Warranty Terms
POTTER ARC-100
Product Overview
The ARC-100 is an analog/addressable releasing fire alarm control panel designed to support up to 100 device addresses, with additional expansion available through multipoint SLC modules. Using the proprietary Potter protocol, the system supports a full range of addressable sensors and modules, with each SLC configured as Class A or Class B and capable of up to 50 ohms of loop impedance.
Equipped with a 5-amp power supply, the ARC-100 includes two 3-amp NACs and two 1-amp Input/Output circuits, all fully programmable for functions such as strobe synchronization, constant power, releasing, door holder control, and more. The panel is fully listed for releasing applications and supports sophisticated suppression logic, including cross-zones, timers, and multi-hazard release outputs.
System expansion is seamless using the PSN-1000 intelligent power supplies, each adding 10 amps of power and additional inputs, with support for up to 31 power supplies. The ARC-100 also offers features such as built-in NFPA 72 compliant smoke sensitivity testing, 99 software zones, P-Link accessory support, and robust system-wide strobe synchronization using Quadrasync technology.
Key Features
- Model Number: ARC-100
- Item Number: 3992755
- Supports 100 addressable points, expandable via multi-point SLC modules
- 99 software zones
- Compatible with Class A or Class B wiring for SLC, NACs, and P-Link
- 5 Amp power supply, expandable to 310 Amps with PSN-1000 series
- NAC Outputs: 3 Amps each, regulated with strobe synchronization
- I/O Circuits: 1 Amp each, regulated, fast-acting for release/abort devices
- NFPA 72 compliant built-in smoke sensitivity test
- System-wide Quadrasync strobe synchronization
- Supports up to 31 intelligent power supplies
- SLC Impedance: Up to 50 ohms, NEC-compliant wiring
- Enclosure: 16-gauge cold rolled steel, locking door with Lexan window
- Dimensions: 16" W × 17" H × 3 7/8" D
- AC Input: 3.0A @ 120VAC or 2.0A @ 240VAC
- Battery Charger: Supports 8–55 Ah, 27.3VDC charging voltage
- P-Link Output: 1 Amp maximum
- Standby Current: 130 mA
- Alarm Current: 200 mA
- Operating Range: 32°F–120°F (0°C–49°C), up to 93% non-condensing humidity