Warranty Terms
POTTER PFC-5008
Product Overview
The PFC-5008 is a microprocessor-based conventional fire alarm control panel designed for small to medium-sized commercial, residential, multifamily, institutional, and industrial facilities. It is built on the PFC-5004E platform and comes from the factory with the ZA-42 expansion module installed, providing eight initiating zones. The preassembled kit also includes provisions for digital communication, although the panel does not include the DACT.
This model features 8 Class B initiating circuits that can be reconfigured as 4 Class A circuits, along with 4 Class A/B indicating circuits rated at 1.7 amps each. A built-in 5-amp power supply supports system operation and provides a 24 VDC, 100 mA resettable regulated output for four-wire smoke detectors. Configuration is fully handled through simple DIP switch programming for easy setup across a wide range of applications.
Key Features
-
Model Details
Model Number: PFC-5008
Item Number: 3992275
Based on PFC-5004E with integrated ZA-42 expansion
DACT not included
-
Initiating & Indicating Circuits
• 8 Class B (Style B) initiating circuits, configurable as 4 Class A (Style D)
• 4 Class A/B (Style Z/Y) indicating circuits with individual trouble indicators
• 1.7 A max per indicating circuit
• Indicating circuits selectable as silenceable or non-silenceable
• Audible output options: Steady, Temporal, California Code, March Time
• Alarm verification selectable on initiating circuits
• Waterflow and supervisory circuit configuration options
-
System Functions & Outputs
• 5-amp power supply
• 24 VDC regulated smoke detector output (100 mA max)
• 24 VDC unfiltered output (300 mA max) for PRTI or remote annunciators
• Auxiliary relays for Common Alarm, Trouble, and Supervisory
• Supervisory relay becomes a second alarm relay when no supervisory zones are used
• Zone disconnect switches
• Built-in walk test mode
• Auto signal silence
• Extensive transient protection
-
Communication & Expansion
• Integrated RS-485 interface
• Supports up to 3 RA8F multiplexed remote annunciators
• Interface for remote trouble indicator
• DIP-switch configuration for all programmable features